Analysis of Boiler # 2 Start up vent line

Venkataswamy, MA and Sujata, M and Parameswara, MA and Bhaumik, SK (2004) Analysis of Boiler # 2 Start up vent line. Project Report. National Aerospace Laboratories, Bangalore.

Full text not available from this repository. (Request a copy)

Abstract

A fractured vent line tube was sent to the laboratory for analysis. The failure of the tube was by thin lip rupture caused due to rapid overheating. Compositional analysis indicated that the failed tube is made of plain carbon steel and does not conform to specification of 2.5Cr-1.0Mo steel.

Item Type: Proj.Doc/Technical Report (Project Report)
Uncontrolled Keywords: Boiler vent line;rapid overheating;thin lip rupture
Subjects: AERONAUTICS > Aeronautics (General)
CHEMISTRY AND MATERIALS > Chemistry and Materials (General)
Division/Department: Materials Science Division, Materials Science Division, Materials Science Division, Materials Science Division
Depositing User: Mrs Manoranjitha M D
Date Deposited: 21 Jul 2011 10:00
Last Modified: 21 Jul 2011 10:00