Failure analysis of boiler tube and wash water line

Venkataswamy, MA and Keshab, Barai and Bhaumik, SK (2003) Failure analysis of boiler tube and wash water line. Project Report. National Aerospace Laboratories, Bangalore.

Full text not available from this repository. (Request a copy)

Abstract

Three specimens belonging to failed boiler tube, wash water line and intermediate tube sheet of furnace were forwarded to the laboratory for analysis. Investigation revealed that the boiler tube had failed by stress rupture due to prolonged over heating and the wash water line had failed by sulphide cracking due to sensitization of the stainless steel tube during welding. The fracture surface of the intermediate tube sheet of the furnace was completely destroyed due to corrosion and hence no study could be carried out.

Item Type: Proj.Doc/Technical Report (Project Report)
Uncontrolled Keywords: Boiler tube;wash water line;scaling;sensitization;sulphide cracking;stress rupture
Subjects: AERONAUTICS > Aeronautics (General)
CHEMISTRY AND MATERIALS > Chemistry and Materials (General)
Division/Department: Materials Science Division, Materials Science Division, Materials Science Division
Depositing User: Mrs Manoranjitha M D
Date Deposited: 14 Jul 2011 16:26
Last Modified: 14 Jul 2011 16:26
URI: http://nal-ir.nal.res.in/id/eprint/9398